GOSSEN METRAWATT GMBH 23
See 2.4.2.2 for the contents of the function field (FF)
The first character of the data block is the configuration "sensor type". The second character (B marking) cannot be stored, but a character (any, e.g.
00h) must be sent.
3.6.2 Send a control parameter, for example
The parameter index (PI) is not 3xh, thus the characters "from/to channel" and "receipt No." = 1, 1, 0 are contained in the long set.
Example: Send the Heat proportional band Pb I = 2.3% to R2600/01 with the address = 1 (see 4.2).
Transmission from master (long set, see 2.3):
See 2.4.2.2 for the contents of the function field (FF)
According to 4.2 and 2.4.4, the two characters of the data block (17h, 00h) are calculated to be: Pb I in 0.1% = 23 = 0017h
Acknowledgement from equipment (short set):
10h 00h „FF“ „FF“ 16h
PS
68h 08h 08h 68h 01h 69 10h 01h 01h 00h 17h 00h 93h 16h
FF PI PS
Acknowledgement from equipment (short set):
10h 01h „FF“ „FF“ + 1 16h
PS
Data block